Typical Structure and Parameter of OPPC
Double stranded conductor
OrderType model |
OPPC-2S 1/24(M109/R58-326) |
OPPC-2S 1/36(M150/R76-400) |
Max.fiber count |
24 |
36 |
Tube size |
Φ2.7mm |
Φ3.0mm |
Cable diameter |
Φ14.0mm |
Φ16.40mm |
Cable diameter |
37.39mm2 |
50.56mm2 |
Cable diameter |
71.27mm2 |
90.55mm2 |
Cross-section cary area |
108.67mm2 |
150.11mm2 |
Cable weight |
466kg/km |
631kg/km |
(RTS)Rated Tensile Strength(RTS) |
58.4kN |
77.5kN |
20°C DC resistance at 20°C |
0.344Ω/km |
0.247Ω/km |
Safe current-carrying capacity |
325.7A |
399.7A |
Linear expansion coefficient |
17.0x10-6/°C |
17.0x10-6/°C |
Young's modulus |
92.5kN/mm2 |
91.7kN/mm2 |
Corresponding wires model |
LGJ-70/40 |
LGJ-95/55 |
Structure Drawing

Double stranded conductor
OrderType model |
OPPC-3S 1/24(M269/R75-624) |
OPPC-3S 1/48(M208/R64.8-520) |
Max.fiber count |
24 |
48 |
Tube size |
Φ2.5mm |
Φ2.5mm |
Cable diameter |
Φ21.6mm |
Φ19.0mm |
Cable diameter |
29.85mm2 |
29.85mm2 |
Cable diameter |
239.2mm2 |
178.62mm2 |
Cross-section carry area |
269.05mm2 |
208.48mm2 |
Cable weight |
881kg/km |
705kg/km |
Rated Tensile Strength(RTS) |
74.8kN |
64.8kN |
DC resistance at 20°C |
0.1160/km |
0.152Q/km |
Safe current -carrying capacity |
624.4A |
520.1A |
Linear expansion coefficient |
20.3x10-6/°C |
19.9x10-6/°C |
Young's modulus |
67.8kN/mm2 |
124.3kN/mm2 |
Corresponding wires model |
LGJ-240/30 |
LGJ-185/30 |
Structure Drawing


Weather condition
Temperature(C) |
Wind speed (m/s) |
lce thickness (mm) |
|
Lowest temperature |
|||
Average temperature in year |
|||
Maximum wind speed |
|||
Ice thickness |
|||
Highest temperature |
|||
Installation |